INSTALLATION PROCEDURES
GROWMASTER SERIES OF CONTROLLERS
PANEL MOUNTING
Mount the control panel in an accessible location. Make sure that the location is free of vibration and in close
proximity to the devices being controlled. Always consider voltage drop of electrical current when locating the
control panel. Securely mount the panel.
SWITCHING CONTACTORS AND RELAYS
The control panel will operate the greenhouse equipment via load contactors and load relays. ALL RELAYS
AND LOAD CONTACTORS USED MUST HAVE A SURGE SUPPRESSOR INSTALLED ACROSS THE
COIL OF THE RELAY OR LOAD CONTACTOR. These surge suppressors are readily available from Micro
Grow Greenhouse Systems, Inc. All load contactors and relays are also readily available from Micro Grow
Greenhouse Systems, Inc. To decide which to use, follow this guide:
LOAD CONTACTORS: Exhaust fans, pad pumps, horizontal air flow fans, heating pumps, fan jets, large
heaters, crop lighting, and all other larger electrical loads over 1/6 H.P.
LOAD RELAYS: Signal switching such as the small control lines for gas fired heaters, control lines for vent
and shade system controls, small loads such as motorized shutters, other loads up to 1/6 H.P.
CUSTOM CONTACTOR AND RELAY PANEL AVAILABLE A custom built load contactor and load relay
panel is available from Micro Grow Greenhouse Systems, Inc. This panel will contain all of the required
switching apparatus for your project, as well as a correctly sized machine tool transformer. Contact Micro
Grow Greenhouse Systems, Inc. for pricing and availability.
TRANSFORMERS
A 24 VAC transformer will power the control panel. It is important to use a MACHINE TOOL type. A Machine
Tool Transformer is a heavy-duty variety that will allow for high inrush currents that are associated with the use
of load contactors and relays. Micro Grow Greenhouse Systems, Inc. stocks these types of transformers.
Use no smaller than a 50 VA Machine Tool Transformer. For a system that has more than three load
contactors connected, use a 100 VA Machine Tool Transformer.
ELECTRICAL CIRCUITS
The electrical circuit that feeds the machine tool transformer must have no other loads connected to it. This
will prevent damaging surges from other related electrical devices. Follow all local and national codes in the
connection of all of the greenhouse equipment. Always allow for voltage drop conditions. Always consider
that the greenhouse is a wet environment. Always follow the code rulings for disconnect switches and
overcurrent devices on greenhouse equipment. USE A QUALIFIED AND LICENSED ELECTRICIAN AT ALL
TIMES.