Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will
install heater plus any adjoining rooms with
doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________
cu. ft. (volume of space)
Example: Space size 20 ft. (6.1 m)
(length) x 16 ft. (4.88 m) (width) x
8 ft. (2.44 m) (ceiling height) = 2560 cu.
ft. (72.49 m
3
) (volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to deter-
mine the maximum Btu/Hr the space can
support.
________(volume of space) x 20 =
(Maximum Btu/Hr the space can support)
Example: 2560 cu. ft. (72.49 m
3
) (volume
of space) x 20 = 51,200 (maximum Btu/
Hr the space can support)
3. Add the Btu/Hr of all fuel burning appli-
ances in the space.
Vent-free heater _________ Btu/Hr
Gas water heater* _________ Btu/Hr
Gas furnace _________ Btu/Hr
Vented gas heater _________ Btu/Hr
Gas replace logs _________ Btu/Hr
Other gas appliances*+ _______ Btu/Hr
Total = ________ Btu/Hr
* Do not include direct-vent gas appli-
ances. Direct-vent draws combustion
air from the outdoors and vents to the
outdoors.
AIR FOR COMBUSTION AND VENTILATION
30,000
26,000
56,000
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m
3
per kw) of the aggregate
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet per
1,000 Btu/hr (4.8 m
3
per kw) of the aggregate
input rating of all appliances installed in that
space. Rooms communicating directly with the
space in which the appliances are installed*,
through openings not furnished with doors, are
considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Conned or Unconned Space
Example:
Gas water heater __________ Btu/Hr
Vent-free heater + _________ Btu/Hr
Total = _________ Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
_______Btu/Hr (maximum can support)
_______Btu/Hr (actual amount used)
Example: 51,200 Btu/Hr (maximum the
space can support)
56,000 Btu/Hr (actual amount
of Btu/Hr used)
The space in the above example is a conned
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can sup-
port. You must provide additional fresh air.
Your options are as follows:
A. Rework worksheet, adding the space
of an adjoining room. If the extra space
provides an unconned space, remove
door to adjoining room or add ventilation
grills between rooms. See Ventilation Air
From Inside Building, page 9.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 9.
C. Install a lower Btu/Hr heater, if lower Btu/
Hr size makes room unconned. If the ac-
tual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space
is an unconned space. You will need no
additional fresh air ventilation.